F: Ik moat in 220 kV-kabel testje, 8 km lang. Hokker SR-wurdearring haw ik nedich?
A: 7-stap sizing proseduere: bepale test easken → berekkenje C → skatting L → berekkenje f_res → ferifiearje wurdearrings → iterate → finalize.
Stap-foar-stap - 220 kV kabel, 8 km:
1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Duration 60 min.
2. C ≈ 8 km × 0,2 μF/km=1.6 μF.
3. Beskôgje 3× 100 kV/2 A reaktors yn parallel: L=26.7 H, f=24.4 Hz.
4. Strom op 254 kV: I=V × 2πf × C=6.9 A. Mar 3×2A → 6A totaal → NET OK.
5. Upgrade nei 3× 100 kV / 4 A reaktors: totaal I=12 A → OK. P_in=254×6.9/35=50 kW.
6. Totaal gewicht: 3 × 450 kg + 200 + 150 + 100=~ 1.800 kg.
Gearfetting fan grutte foar mienskiplike senario's:
|
Senario |
V_test (kV) |
C (μF) |
f (Hz) |
Oanrikkemandearre Systeem |
|
33 kV kabel, 3 km |
48 |
0.6 |
45 |
60 kV/2A × 1, 5 kW |
|
110 kV kabel, 5 km |
160 |
1.0 |
24 |
200 kV/4A × 2, 20 kW |
|
220 kV kabel, 8 km |
254 |
1.6 |
24 |
300 kV/4A × 3, 50 kW |
|
400 kV kabel, 5 km |
330 |
1.0 |
48 |
400 kV/2A × 2, 25 kW |
|
GIS 245 kV, 10 baaien |
230 |
0.05 |
80 |
300 kV/1A × 2, 5 kW |
|
Generator 100 MVA |
28 |
2.5 |
45 |
30 kV/5A, 10 kW |
Krityske herinneringen:
• +20% marzje op reactor voltage rating. +30% marzje op hjoeddeistige wurdearring.
• As P_in> 100 kW, beskôgje seksjonele testen (tastien troch de measte noarmen).
• Werklike Q kin leger wêze as skatte - konservative planning foarkomt fjildfalen.